Space Saver

The ultimate protection solution
when space is at a premium

  • Power distribution neatly organized at the back of the rack
  • Advanced Series Mode ® surge elimination technology
  • Impedance Tolerant EMI/RFI filter
  • SurgeX ICE Inrush Current Elimination
  • 100% fail-safe protection, never requires reset
  • Accepts both DC voltage and contact closure control inputs
  • Two or more units can be cascaded together for larger systems
  • A-1-1 Certified
Brochure / Data Sheet

Features

matrix-space-saver-ar

Specifications

 

CM-1115-RT / CM-1120-RT    

Operational Voltage Range

90 to 150 Volts AC

   

Current rating

15/20 Amps

   

Power Rating

1,800/2,400 Watts

   

Maximum Load Inrush Energy

1000 Joules total during power-up

   

Under-Voltage Shutdown

90 V (resume at 100V)

   

Over-Voltage Shutdown

145V (resume at 135V)

   

Surge Let-through Voltage

Zero let-through Voltage for a 6000 Volt surge

   

Meets Federal Guidelines

Grade A, Class 1, Mode 1 (CID A-A-55818)

   

EMI/RFI Filter, Normal Mode

40 dB @ 100 KHz, 50dB @ 300 KHz, 50 dB @ 3 MHz,
50 dB @ 30 MHz (50 Ohm load)

   

EMI/RFI Filter, Common Mode

18dB @ 300 KHz, 30 dB @ 1 MHz, 50 dB @ 5 MHz,
50 dB @ 20 MHz (50 Ohm load)

   

Maximum Applied Surge Voltage

Unlimited, due to current limiting*

   

Maximum Applied Surge Current

Unlimited, due to current limiting*

   

Maximum Applied Surge Energy

1 kV>500,000; 3 kV>10,000;
6 kV>1000

   

Endurance

(C62.41-1991 category B3 pulses), 1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000

   

Number of Outlets

2

   

Remote Control Voltage

5 to 30 Volts DC

   

Remote Control Current Draw

4 mA maximum

   

Contact Closure Max. Resistance

100 Ohms

   

Auxiliary Relay Contact Rating

30 Volts DC at 1 Amp

   

12 Volt Output Max. Current

20 mA

   

Dimensions (no rack ears or feet)

4.95″ W x 9.50″ D x 5.66″ H

   

Weight

8.5 lb.

   

Temperature Range

5º to 35º C

   

Humidity Range

5% to 95% R.H., non-condensing

   

Agency Listings

ETL and cETL (UL 1449, Third Edition, Type 3 Surge Protective Device; UL 1283; CSA C22.2 No.8-M1986, R2004).
Listed as base models SX-1115-RT, SX-1120-RT.

   


*1.2 x 50 μs pulse, industry standard combination wave surge, as per IEEE C62.41

CAUTION: Do not install this device if there is not at least 10 meters (30 feet) or more between the electrical outlet and the electrical service panel.

Downloads

User Manual:
CM-1115-RT-AR
Software Version: 1.01.04
Firmware Version: 1.01.06
Download
Quick Start:
CM-1115-RT-AR
Software Version 2.0
Download
User Manual:
CM-1115-RT
CM-1120-RT
CM-1115-RT18
CM-1120-RT18
CM-1115-RT24
CM-1120-RT24
Version 2.0
Download

Axess Ready

DMU
(Device Management Utility)
Current version is 1.30.11
Download
Current Firmware FileCurrent version 1.10.169
Download
DXP Example filesVersion 2.0
Download

Product / Warranty Registration

Product/Warranty Registration
Register

Warranty

Warranty
Download